This special compound also offers high insulation resistance and dielectric strength. These ISI marked wires meet the latest requirements of IS 694:1990 of flame retardant properties which means extra protection against electric shocks, short circuits and fires BIL Cable’s wires are energy efficient as only Electrolytic Copper Conductors of 99.97% purity having very low resistance are used thus ensuring low energy losses.
Nominal area of conductor |
Number/Nom.Dia.of Wires |
Thickness Insulation(Nom.) |
Approx.Overall Diameter |
Current Carrying Capacity*2 wires single phase |
Resistance(Max.) per km. @20°C
|
Sq. mm |
No./mm |
mm |
mm |
Amps. |
Ohms |
0.75 |
24/0.20 |
0.6 |
2.50 |
8 |
26.00 |
1.0 |
14/0.30 |
0.7 |
2.80 |
14 |
18.10 |
1.5 |
22/0.30 |
0.7 |
3.10 |
18 |
12.10 |
2.5 |
36/0.30 |
0.8 |
3.80 |
24 |
7.41 |
4.0 |
56/0.30 |
0.8 |
4.40 |
32 |
4.95 |
6.0 |
84/0.30 |
0.8 |
5.00 |
40 |
3.30 |
Standard Colours : Red, Yellow, Blue, Black, Green, White and Grey
Supplied in 90 meter coil in attractive cartons. Confirm to IS 694:1990.
*As per IS 3961 (Part V)-1968
Critical Oxygen Index |
ASTM-D 2863 |
More than 29% |
Temperature Index |
ASTM-D 2863 |
More than 250°C |
• Triple Insulated Wire offers extra protection against pinholes
• Easy laying in conducts
• No sparking and over heating
• Saves electricity cost
• Anti-rodent & termite
• UV resistance